9.7 Pit data register block

Registers in this block can be read by means of function codes
0x03 and/or 0x04. It is not possible to write to these registers.
0xFFFF indicates that the data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
00301
WaterLevel
00302
MaxWaterLevel
00303
PowerHI
00304
PowerLO
00305
EnergyTripCntHI
00306
EnergyTripCntLO
00307
OnTimeCntHI
00308
OnTimeCntLO
00309
OprTimeTripCntHI
00310
OprTimeTripCntLO
00311
PumpOperationTimePct
00312
MultiPumpOperationTimePct
00313
MultiPumpOperationTimeMax
00314
DigitalInput
Scale
Description
Average of the pit water level as estimated by the pumps.
0.01 m
Used in single-pit mode only. Pit mode: 0. Pit mode is set in register 00203.
Maximum value that the pit water level has had.
0.01 m
Can be reset with register 00101, bit 1: ResetHistory.
Used in single-pit mode only. Pit mode: 0. Pit mode is set in register 00203.
1 W
Pit power consumption.
Pit energy consumption.
1 kWh
Can be reset with register 00101, bit 1: ResetHistory.
Power-on time for the CIU.
1 minute
Cannot be reset.
Pit operating time where one or more pumps have been operating.
1 minute
Can be reset with register 00101, bit 1: ResetHistory.
Percentage of time where one or more pumps have been operating within the
last 30 days.
0.01 %
Can be reset with register 00101, bit 1: ResetHistory.
Used in single-pit mode only. Pit mode: 0. Pit mode is set in register 00203.
Percentage of the pump operating time where more than one pump have
been operating within the last 30 days.
0.01 %
Can be reset with register 00101, bit 1: ResetHistory.
Used in single-pit mode only. Pit mode: 0. Pit mode is set in register 00203.
Logged value of maximum pump operating time where more than one pump
have been operating continuously within the last 30 days.
1 second
Can be reset with register 00101, bit 1: ResetHistory.
Used in single-pit mode only. Pit mode: 0. Pit mode is set in register 00203.
Bits
Digital inputs.
27