9.10 Pump 3 register block

All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name
00501
Pump3.MotorTemperature
00502
Pump3.ElectronicTemperature
00503
Pump3.AverageLineVoltage
00504
Pump3.AverageLineCurrent
00505
Pump3.AverageLineCurrentLatest
00506
Pump3.LineFrequency
00507
Pump3.PhaseSequence
00508
Pump3.CosPhi
00509
Pump3.Power
00510
Pump3.EnergyTripCounterHI
00511
Pump3.EnergyTripCounterLO
00512
Pump3.WaterLevel
00513
Pump3.WaterLevelMax
00514
Pump3.MaxContinousTime
00515
Pump3.TotalPoweredTimeHI
00516
Pump3.TotalPoweredTimeLO
00517
Pump3.OperationTimeHI
00518
Pump3.OperationTimeLO
00519
Pump3.OperationTimeTripCounterHI
00520
Pump3.OperationTimeTripCounterLO
00521
Pump3.NumberOfStartsHI
00522
Pump3.NumberOfStartsLO
00523
Pump3.NumberOfStartsTripCounterHI
00524
Pump3.NumberOfStartsTripCounterLO
00525
Pump3.AlarmCode
00526
Pump3.WarningCode
00527
Pump3.OperatingMode
Bit 0: Subpump3AlarmsPhaseSequence
Bit 1: Subpump3AlarmsOvervoltage
Bit 2: Subpump3AlarmsUndervoltage
Bit 3: Subpump3AlarmsOverload
Bit 4: Subpump3AlarmsBlockedMotor
Bit 5: Subpump3AlarmsAlarmBit5
Bit 6: Subpump3AlarmsMotorTemperature
00528
Bit 7: Subpump3AlarmsElectronicTemperature
Bit 8: Subpump3AlarmsTermoRelay1
Bit 9: Subpump3AlarmsTermoRelay2
Bit 10: Subpump3AlarmsVerificationError
Bit 11: Subpump3AlarmsAlarmBit11
Bit 12: Subpump3AlarmsSensorFault
Bit 13: Subpump3AlarmsAlarmBit13
32
Scale
Description
0.01 K
Motor temperature, pump 3.
0.01 K
Electronics temperature, pump 3.
0.1 V
Average supply voltage, pump 3.
0.1 A
Average supply current, pump 3.
Average supply current the last time pump 3 was
0.1 A
operating.
0.1 Hz
Frequency of power supply, pump 3.
Bool
Phase sequence of power supply, pump 3.
0.01
Power factor, pump 3.
1 W
Power consumption, pump 3.
Energy consumption, pump 3.
1 kWh
Can be reset with register 00101, bit 4:
PitPump3ResetHistory.
0.01 m
Water level as estimated by pump 3.
Logged maximum value of water level, pump 3.
0.01 m
Can be reset with register 00101, bit 4:
PitPump3ResetHistory.
Logged maximum value of continuous operating time
within the last 30 days, pump 3.
1 minute
Can be reset with register 00101, bit 4:
PitPump3ResetHistory.
Total time that pump 3 has been powered on.
1 minute
Used as time stamp for alarms in the alarm log the
moment the alarm appears.
1 minute
Total time that pump 3 has been operating.
Trip counter of the total time that pump 3 has been
operating.
1 minute
Can be reset with register 00101, bit 4:
PitPump3ResetHistory.
Unscaled
Total number of starts, pump 3.
Unscaled
Trip counter of total number of starts, pump 3.
Grundfos-specific alarm code, pump 3.
Unscaled
See section
14.2 CIU
Grundfos-specific warning code, pump 3.
Unscaled
See section
14.2 CIU
Operating mode of pump 3.
0: "Auto" mode (power-on default)
Bits
1: Forced start
2: Forced stop.
Phase sequence reversed
Overvoltage
Undervoltage
Overload
Blocked motor/pump
-
Motor temperature
Temperature, control electronics
Temperature relay 1 in motor, for example Klixon
Temperature relay 2 in motor, for example thermistor
Verification error, code area (ROM, FLASH)
-
Sensor fault
-
262.
262.