Grundfos CIU 202 Functional Profile And User Manual page 29

Modbus for seg autoadapt, modbus rtu, 3g/4g cellular, ethernet for modbus tcp
Table of Contents

Advertisement

Address Register name
Bit 0: Subpump1WarningsWarningsPhaseSequence
Bit 1: Subpump1WarningsOvervoltage
Bit 2: Subpump1WarningsUndervoltage
Bit 3: Subpump1WarningsOverload
Bit 4: Subpump1WarningsBlockedMotor
Bit 5: Subpump1WarningsAlarmBit5
Bit 6: Subpump1WarningsMotorTemperature
00429
Bit 7: Subpump1WarningsElectronicTemperature
Bit 8: Subpump1WarningsTermoRelay1
Bit 9: Subpump1WarningsTermoRelay2
Bit 10: Subpump1WarningsVerificationError
Bit 11: Subpump1WarningsAlarmBit11
Bit 12: Subpump1WarningsSensorFault
Bit 13: Subpump1WarningsAlarmBit13
Scale
Description
Phase sequence reversed
Overvoltage
Undervoltage
Overload
Blocked motor or pump
-
Motor temperature
Temperature, control electronics
Temperature relay 1 in motor, for example Klixon
Temperature relay 2 in motor, for example thermistor
Verification error, code area (ROM, FLASH)
-
Sensor fault
-
29