9.5 Pit control and configuration register block

Registers in this block can be read by means of function codes
0x03 and/or 0x04. They can be written as holding registers with
function code 0x06 and 0x10.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
Bit 0: ResetAlarm
Bit 1: ResetHistory
Bit 2: PitPump1ResetHistory
Bit 3: PitPump2ResetHistory
00101
Bit 4: PitPump3ResetHistory
Bit 5: PitPump4ResetHistory
Bit 6: PitPump1ResetAlarm
Bit 7: PitPump2ResetAlarm
Bit 8: PitPump3ResetAlarm
20
Scale
Description
Control bit that resets system alarms and warnings.
0: No resetting
1: Resetting alarm.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets pit history.
0: No resetting
1: Resetting history.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets counters in pump 1.
0: No resetting
1: Resetting history.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets counters in pump 2.
0: No resetting
1. Resetting history.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets counters in pump 3.
0: No resetting
1: Resetting history.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets counters in pump 4.
0: No resetting
1: Resetting history.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets alarms and warnings from pump 1.
0. No resetting
1: Resetting alarm.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets alarms and warnings from pump 2.
0: No resetting
1: Resetting alarm.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
Control bit that resets alarms and warnings from pump 3.
0: No resetting
1: Resetting alarm.
Bool
This control bit is triggered on rising edge only, meaning setting logical 0 to
1.
See section
9.2 CIM configuration register
acknowledgement behaviour.
block, address 00005, for
block, address 00005, for
block, address 00005, for
block, address 00005, for
block, address 00005, for
block, address 00005, for
block, address 00005, for
block, address 00005, for
block, address 00005, for