Address
Register name
Bit 0:
Pitpump1CommFault
Bit 1:
Pitpump2CommFault
00233
Bit 2:
Pitpump3CommFault
Bit 3:
Pitpump4CommFault
00234
OperatingMode
Bit 0: WarningInPumpOrPit
Bit 1: AlarmInPumpOrPit
00235
Bit 2: RESERVED
Bit 3: ManualControlStatus
00236
SignalLevelActual
00237
SignalLevelAverage
00238
IPAddressHI
00239
IPAddressLO
Bit 0: AlarmBitsExternalFault
Bit 1: AlarmBitsCommunicationFault
Bit 2: RESERVED
Bit 3: AlarmBitsPump1Fault
00240
Bit 4: AlarmBitsPump2Fault
Bit 5: AlarmBitsPump3Fault
Bit 6: AlarmBitsPump4Fault
Bit 7: AlarmBitsSensorLimit2Exceeded
Bit 8: AlarmBitsSetupConflict
Bit 0: RESERVED
Bit 1: WarningBitsCommunicationFault
00241
Bit 2: WarningBitsVerificationError
Bit 3 -7: RESERVED
Bit 8: WarningBits.SetupConflict
26
Scale
Description
Indicates if there is a communication fault on pump 1.
Bool
0: No fault
1: Fault.
Indicates if there is a communication fault on pump 2.
Bool
0: No Fault
1: Fault.
Indicates if there is a communication fault on pump 3.
Bool
0: No fault
1: Fault.
Indicates if there is a communication fault on pump 4.
Bool
0: No fault
1: Fault.
Used in single-pit mode only. Pit mode: 0.
Operating mode of the pump pit.
0: Standby
1: Startup delay
2: Pumping (level control)
Enum
5: Stopped (level control)
9: Manuel control (all enabled pumps in manual control mode)
11: Mains supply failure
13: Alarm on all enabled pumps
14: All pumps out of operation.
Main status of warning(s).
0: No warning(s)
1: Warning(s) on a pump or in the pit.
Main status of alarm(s).
0: No alarm(s)
1: Alarm(s) on a pump or in the pit.
-
Main status of manual pump control.
0: No manual pump control enabled (full "Auto")
1: Manual pump control enabled (partly or completely).
1 %
Actual level of cellular network signal. CIM 260 only
1 %
Average level of cellular network signal. CIM 260 only
Unscaled IP address for data communication. CIM 260 only
External fault signal
Communication fault, pump
-
Pump 1 fault
Pump 2 fault
Pump 3 fault
Pump 4 fault
Sensor limit 2 exceeded (High level)
Setup conflict
-
Communication fault, pump
Verification error, code area (ROM, FLASH)
-
Setup conflict