Cim Status Register Block; Cellular Network Real Time Clock - Grundfos CIU 202 Functional Profile And User Manual

Modbus for seg autoadapt, modbus rtu, 3g/4g cellular, ethernet for modbus tcp
Table of Contents

Advertisement

9.3 CIM status register block

Registers in this block can be read by means of function codes
0x03 and/or 0x04. They are read-only. Use this block for various
kinds of fault finding.
Address Register name
00021
GENIbusCRCErrorCnt
00022
GENIbusDataErrorCnt
00023
VersionNumber
00024
ActualModbusAddress
00025
GENIbusTXcountHI
00026
GENIbusTXcountLO
00027
GENIbusRXcountHI
00028
GENIbusRXcountLO
GeneralStatus
Bit 0: ScadaPinCodeEnabled
00029
GeneralStatus
Bit 1: WriteAccess
00030
UnitFamily
00031
UnitType
00032
UnitVersion
00033
BatteryState
00034
ProductSoftwareVersionHI
00035
ProductSoftwareVersionLO
00036
ProductSoftwareDayMonth
00037
ProductSoftwareYear

9.4 Cellular network real time clock

Address
Register name
00080
SetUNIXRealTimeClockHI
00081
SetUNIXRealTimeClockLO
00082
SetRtcSecond
00083
SetRtcMinute
00084
SetRtcHour
00085
SetRtcDay
00086
SetRtcMonth
00087
SetRtcYear
00088
Bit 0: SetRtc
00089
StatusUNIXRealTimeClockHI
00090
StatusUNIXRealTimeClockLO
00091
StatusRtcSecond
00092
StatusRtcMinute
00093
StatusRtcHour
00094
StatusRtcDay
00095
StatusRtcMonth
00096
StatusRtcYear
00097
Bit 0: StatusSetRTCAck
Description
Holds a CRC error counter for the GENIbus connection to the product.
Holds a data error counter for the GENIbus connection to the product.
A Grundfos-specific version number. This is an unsigned integer value.
Holds the current Modbus slave address of the device.
Valid value range: 1...247.
Holds a transmit counter for the total number of telegrams sent to the
product on the GENIbus connection.
Holds a receive counter for the total number of telegrams received from the
product on the GENIbus connection.
PIN code functionality.
0: No PIN code required
1: PIN code required to perform remote control and configuration.
Activation of SCADA PIN code protection takes place via the SMS
command "SCADACODE". See "CIM 260 SMS commands" which you can
download from Grundfos Product Center.
Remote write access.
0: No write access, the PIN code is incorrect.
1: Full write access, the PIN code is either correct or not enabled.
Grundfos product family.
Grundfos product type.
Grundfos product version.
State of battery
0: Battery not present
1: Battery must be replaced
2: Battery charging
3: Battery needs charging, but temperature too high
4: Battery needs charging, but temperature too low
5: Battery low
6: Battery OK
255: Battery state not available
Product software version (BCD diget 1-4 aa.bb)
Product software version (BCD diget 5-8 cc.dd)
Product software date (BCD ddmm)
Product software date (BCD yyyy)
Description
Set real time clock (32 bit UNIX format)
Triggered on value change
Set real time clock - seconds
Set real time clock - minutes
Set real time clock - hours
Set real time clock - day
Set real time clock - month
Set real time clock - year
Triggers setting of real time clock - s/m/h/d/m/y format
Real time clock (32 bit UNIX format)
Real time clock - seconds
Real time clock - minutes
Real time clock - hours
Real time clock - day of month
Real time clock - month
Real time clock - year (after 2000)
Acknowledge of set RTC command
CIM
CIM
CIM
200
260
500
-
-
-
-
CIM
CIM
CIM
200
260
500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ciu 262Ciu 502

Table of Contents