9. Modbus register overview

9.1 Register block overview

The Modbus registers are grouped in the following register
blocks:
Starting
Register block
address
00001
CIM configuration
00021
CIM status
00101
Pit control and configuration
00201
Pit status
00301
Pit data
00401
Pump 1
00451
Pump 2
00501
Pump 3
00551
Pump 4
00701
Alarm simulation
00751-00800
User registers
All addresses contain registers. Some are bit-interpreted while
others are 16-bit values, or part of 32-bit values. A data value of
65535 (0xFFFF) indicates "not available" when reading registers.
The value of 65535 (0xFFFF) does not imply a "disable" when
writing values.
Each register block will be specified in more detail in the following
sections.
16
Permissions
Description
R/W
Configuration of the CIM module.
R
Status registers for the CIM module.
W
Registers for control and configuration of wastewater pit.
R
Registers for status from wastewater pit.
R
Registers for measured values from wastewater pit.
R
Registers containing pump 1 data and status.
R
Registers containing pump 2 data and status.
R
Registers containing pump 3 data and status.
R
Registers containing pump 4 data and status.
R/W
Features for simulation of alarms and warnings.
R/W
This area is for device labelling by the user.