9.11 Pump 4 register block

All register values are read-only, and 0xFFFF indicates that the
data value is not available.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address Register name
00551
Pump4.MotorTemperature
00552
Pump4.ElectronicTemperature
00553
Pump4.AverageLineVoltage
00554
Pump4.AverageLineCurrent
00555
Pump4.AverageLineCurrentLatest
00556
Pump4.LineFrequency
00557
Pump4.PhaseSequence
00558
Pump4.CosPhi
00559
Pump4.Power
00560
Pump4.EnergyTripCounterHI
00561
Pump4.EnergyTripCounterLO
00562
Pump4.WaterLevel
00563
Pump4.WaterLevelMax
00564
Pump4.MaxContinousTime
00565
Pump4.TotalPoweredTimeHI
00566
Pump4.TotalPoweredTimeLO
00567
Pump4.OperationTimeHI
00568
Pump4.OperationTimeLO
00569
Pump4.OperationTimeTripCounterHI
00570
Pump4.OperationTimeTripCounterLO
00571
Pump4.NumberOfStartsHI
00572
Pump4.NumberOfStartsLO
00573
Pump4.NumberOfStartsTripCounterHI
00574
Pump4.NumberOfStartsTripCounterLO
00575
Pump4.AlarmCode
00576
Pump4.WarningCode
00577
Pump4.OperatingMode
Bit 0: Subpump4AlarmsPhaseSequence
Bit 1: Subpump4AlarmsOvervoltage
Bit 2: Subpump4AlarmsUndervoltage
Bit 3: Subpump4AlarmsOverload
Bit 4: Subpump4AlarmsBlockedMotor
Bit 5: Subpump4AlarmsAlarmBit5
Bit 6: Subpump4AlarmsMotorTemperature
00528
Bit 7: Subpump4AlarmsElectronicTemperature
Bit 8: Subpump4AlarmsTermoRelay1
Bit 9: Subpump4AlarmsTermoRelay2
Bit 10: Subpump4AlarmsVerificationError
Bit 11: Subpump4AlarmsAlarmBit11
Bit 12: Subpump4AlarmsSensorFault
Bit 13: Subpump4AlarmsAlarmBit13
34
Scale
Description
0.01 K
Motor temperature, pump 4.
0.01 K
Electronics temperature, pump 4.
0.1 V
Average supply voltage, pump 4.
0.1 A
Average supply current, pump 4.
Average supply current the last time pump 4 was
0.1 A
operating.
0.1 Hz
Frequency of power supply, pump 4.
Bool
Phase sequence of power supply, pump 4.
0.01
Power factor, pump 4.
1 W
Power consumption, pump 4.
Energy consumption, pump 4.
1 kWh
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
0.01 m
Water level as estimated by pump 4.
Logged maximum value of water level, pump 4.
0.01 m
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
Logged maximum value of continuous operating time
within the last 30 days, pump 4.
1 minute
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
Total time that pump 4 has been powered on.
1 minute
Used as time stamp for alarms in the alarm log the
moment the alarm appears.
1 minute
Total time that pump 4 has been operating.
Trip counter of the total time that pump 4 has been
operating.
1 minute
Can be reset with register 00101, bit 5:
PitPump4ResetHistory.
Unscaled
Total number of starts, pump 4.
Unscaled
Trip counter of total number of starts, pump 4.
Grundfos-specific alarm code, pump 4.
Unscaled
See section
14.2 CIU
Grundfos-specific warning code, pump 4.
Unscaled
See section
14.2 CIU
Operating mode of pump 4.
0: "Auto" mode (power-on default)
Bits
1: Forced start
2: Forced stop.
Phase sequence reversed
Overvoltage
Undervoltage
Overload
Blocked motor or pump
-
Motor temperature
Temperature, control electronics
Temperature relay 1 in motor, for example Klixon
Temperature relay 2 in motor, for example thermistor
Verification error, code area (ROM, FLASH)
-
Sensor fault
-
262.
262.