3. Press MODE button to start the test.
don (Done) will briefly display, then the e7w broadcasts a Commissioning Request into
the room. The device in the room with its Room Gateway function enabled then forwards
the request to INNCOM server.
4. If the INNCOM server received and validated the commission request, it sends a com-
mand back to the Room Gateway that contains the Room ID value. If the e7w receives this
message that containing 5 digit Room ID value, it scrolls the value across its display to
indicate the WAN test passed.
If no Room ID or the incorrect Room ID value scrolls across the e7w display, the WAN test
has failed. Refer to applicable troubleshooting documentation.
Following are the possible reasons for a WAN test failure:
No device in the room is configured to be the Room Gwy or the Room Gateway de-
vice is not powered or configured correctly
The edge router or floor bridge the room communicates through which is not
powered or is not configured correctly
5. Press the FC button to return SERVICE MODE or press UP arrow button to display next
mode.
Or
Press the FC button twice to exit SERVICE MODE.
DOR – Verifying Door Position (dor)
The dor parameter is used to verify room entry door position is being reported into the room. With the
Door test initiated, the e7w will sound its buzzer when the door is open, and the LCD shows the num-
ber of times the door has changed the door position from closed to open.
NOTE
There are two conditions to be satisfied for door test:
There is device in the room that is monitoring and reporting door position via a 0x000281
Entry Door Open message such as an S541. RF.
INNCOM e7w THERMOSTAT USER GUIDE
47
31-00302-01