Timelox Rf Locks - Honeywell INNCOM e7w User Manual

Hide thumbs Also See for INNCOM e7w:
Table of Contents

Advertisement

Timelox RF Locks

1. Verify the Inncom Room Gateway / Timelox Proxy device is configured to support Timelox.
Either verify the software created for the Inncom Proxy has default support to be the Timelox
RF Lock Proxy or activate the applicable I/O Map in the device to configure it to be the Time-
lox RF Lock proxy.
If using a generic "Shelf" software in the Timelox Proxy, I/O Map 65 configures it to support
Timelox.
It is assumed that a PC502.4G is being used as the Timelox RF Lock proxy device for this
procedure.
2. Enter service parameter mode on the e7w
3. Set the desired Room ID, RF Channel, and PAN ID into the e7w that the particular Inncom
Proxy /Room Gateway (typically a PC502.4G) and lock should be using for the particular
room.
4. On the e7w, go to the Adr (Address Teach) parameter and press Mode to view the value.
Change the displayed value to 65, then press the FC button to return back to Adr on the
display.
5. Go to the e7w bnd menu option and press the Mode button.
6. Use the Up/Down arrow buttons to set the value to the address of the device being used as
the Timelox RF Lock Proxy. This will typically be a PC502, address 227, if using an e7w. How-
ever, consult applicable documentation.
7. Press the Fan button on the e7w to make, it sends a 0x00113 Open Bind Window command
to the address defined in step 6. The PC502 will open a 2 minute bind window, waiting to see
a bind request from the lock.
8. Hold the Timelox "Discovery" RFID key card in front of the window on the outside of the lock
for 1-2 seconds.
The lock should rapidly flash the Green LED 2 times.
The lock will broadcast a Bind request message that contains the MAC address of the
lock.
If the PC502 saw the Bind request from the lock, it will respond to the lock with a
Bind Offer telling the lock the RF parameters to adopt. It will also send a Sound
Buzzer message making the e7w beep 3 times, create Registry 193:8:1 to store the
lock's MAC address and finally RESET. This indicates Binding is complete.
9. Perform a Door Test from the e7w (dor test as covered earlier in this document). Open and
close the Door and verify the Lock is reporting door open / close.
You may need to wait 20-30 seconds to allow the PC502/Inncom proxy device to fully startup
following the reset before performing the door test.
INNCOM e7w THERMOSTAT USER GUIDE
67
31-00302-01