PFt – e7w PIR Motion Sensor Filter (PFt)
Use the PFt parameter to adjust the sensitivity of the e7w built in PIR motion sensor.
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select PFt
3. Press MODE to view the value. The value can between 1 and 4.
1. Disable PIR filter and apply no filtering to the signal from the PIR sensor.
2. Report detected motion only after 2 PIR sensor detections occur.
3. Report detected motion only after 3 PIR sensor detections occur.
4. Report detected motion only after 5 PIR sensor detections occur.
Use the UP/DOWN arrow buttons to select the desired value.
4. Press the FAN button to store the change. The e7w will beep
5. Press the FC button to return SERVICE MODE or press UP arrow button to display next
mode
Or
Press the FC button twice to exit SERVICE MODE
CTR – Contractor Mode Parameter (Ctr)
Contractor mode allows conditioning a space during the construction phase to a defined set temper-
ature and locking out the key-pad to prevent tampering.
Follow the below steps to enter and activate Contractor Mode:
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select Ctr.
INNCOM e7w THERMOSTAT USER GUIDE
63
31-00302-01