PFt – e7w PIR Motion Sensor Filter (PFt)
Use the PFt parameter to adjust the sensitivity of the e7w built in PIR motion sensor.
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select PFt
3. Press MODE to view the value. The value can between 1 and 4.
1. Disable PIR filter and apply no filtering to the signal from the PIR sensor.
2. Report detected motion only after 2 PIR sensor detections occur.
3. Report detected motion only after 3 PIR sensor detections occur.
4. Report detected motion only after 5 PIR sensor detections occur.
Use the UP/DOWN arrow buttons to select the desired value.
4. Press the FAN button to store the change. The e7w will beep
5. Press the FC button to return SERVICE MODE or press UP arrow button to display next
mode
Or
Press the FC button twice to exit SERVICE MODE
CTR – Contractor Mode Parameter (Ctr)
Contractor mode allows conditioning a space during the construction phase to a defined set temper-
ature and locking out the key-pad to prevent tampering.
Follow the below steps to enter and activate Contractor Mode:
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select Ctr.
INNCOM e7w THERMOSTAT USER GUIDE
63
31-00302-01