Verifying HVAC Partner Address (PA)

The default e7w partner address is 13, and the default HVAC partner address (X47 or similar) is 14. It
attempts to communicate with its HVAC partner assuming this address. Depending on the require-
ment, the HVAC partner could use a different address, such as 224, to change HVAC partner address,
refer Installation/ Commissioning document.
To change the HVAC Partner address, follow the steps below:
1. Enter Service Mode on the e7w.
2. Press Down arrow button until PA (Partner Address) is displayed.
3. Press MODE button to view the value. Value 14 will be displayed (14 is the default partner
address).
4. Press UP/DOWN arrow button to change the desired partner address.
5. Press FAN button, to store the address value. The unit beep, confirming that the address
value is successful stored in memory.
NOTE: For more details, refer applicable commissioning document.

Binding Auxiliary Devices

Once the e7w is installed and configured with its HVAC Partner Address, the next step is to use either
the e7w or the EngINN software (with the PC503 USB commissioning tool) to commission the other
devices in the room.
NOTE: The e7w can be used as commissioning tool, refer applicable commissioning document for
exact steps.

Binding the RF to S5 Gateway Used by the e7w

In order for the e7w to communicate with any in-room S5 Bus devices, the e7w must be bound to an
RF device in the room that is connected to the S5 Bus. This RF device will typically be a PC502.4G.
Follow the steps below to bind the PC502.4G using the e7w.
1. Enter SERVICE MODE on the e7w.
2. Press UP/DOWN arrow button to select Io.
3. Press MODE button. This action displays Io value.
4. Press UP/DOWN arrow button to change Io value range from 0 to 255, set Io value to the
required I/O map number, typically an I/O map 0 is used.
5. Press FAN button. This action display "bnd" to initiate a Reverse Binding.
6. Press Reset/Bind switch on the PC502.4G (for pressing Rest/Bind switch use a small point
like the end of a straightened paper clip).
After completing of binding, PC502.4G LED flashes and sends a message to make e7w
beep, confirming that binding of e7w with PC502.4G is successful.