The following is a complete example of reading and changing a Group 9 Registry.
Read Registry 9:1 Occupancy, Offset 8 Min_GuestOccupancyTimeout of the HVAC partner to the e7w.
Change from the current value of 10 minutes to 15 minutes.
Press MODE
Use Up/Down button to
set value to 8 , then
press MODE
Press F/C Button 4 times to exit out of rEG menus until Str (Store) appears on display
Use Up/Down button to
select Gr value ,then press
MODE
Value
Current Value is 10.
Use Up arrow button to
change value to 15
Press FAN button to store the changes
INNCOM e7w THERMOSTAT USER GUIDE
Use Up/Down button to
Parameter and value 0 be
select Key value ,then press
displayed. This is Registry 9:1
MODE
Offset 0
Value
Value changed to 15
41
Value
Press FAN button to
store the new value.
Cloud/Sun symbol blinks
to indicate registry
value has been changed
31-00302-01