The following markings have the function:
● Use of proven components
● Suitable for the intended use
● The occurrence of a fault can result in the loss of the safety function.
The probability of a fault occurring is reduced as far as possible by the use of forced contacts.
The use of a single circuit in conjunction with undervoltage release achieves compliance with
safety category 1 to EN 954-1.
Note
This has not been officially certified in Germany.
Connecting
Firstly, the contacts of the EMERGENCY STOP button are integrated into the circuit breaker
control circuit. Secondly, the remaining NC contact is connected to the terminal block.
EMERGENCY STOP button
=.DB-S1001:31-32
Max. connectable cross-section: 4 mm² (AWG 10)
Activation of the circuit breakers is described in the section entitled "Connecting the circuit
breakers".
8.5

Fault and system messages

Hardware trace
The drive saves data to the CompactFlash card each time there is a fault trip. Customer
Supports requires this data in the case of a fault.
Save your data as follows:
1. Switch off the drive.
2. Switch off the power supply for the control cabinet. Remove the CompactFlash card from
3. Save all data of directory "Install\Sinamics\Trace".
4. Send these data to Customer Support.
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions Rev.201910301420 MUSTER
the Control Unit.
Where connected
EMERGENCY STOP customer
Operation
8.5 Fault and system messages
=.DB-X05:9, 10
97