Tripping Of The Circuit-Breaker In Case Of Undervoltage; Fault And System Messages; Indicating And Rectifying Faults - Siemens SINAMICS SH150 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Operation

8.4 Fault and system messages

8.3.1.2

Tripping of the circuit-breaker in case of undervoltage

If a serious fault occurs (e.g. overload in the DC link), the drive is immediately disconnected
from the power supply using the safety shutdown function.
Danger to life as a result of residual voltages at the output terminals
This function cannot ensure that the drive stops immediately, nor can it ensure that residual
voltages do not still exist at the output terminals and within the device itself.
High voltages can cause death or serious injury if the safety rules are not observed or if the
equipment is handled incorrectly.
● Always carefully observe the "five safety rules (Page 13)".
The shutdown of the circuit-breaker is triggered by a safety contactor combination.
The plant-side circuit-breaker must be equipped with an undervoltage trip to ensure the wire-
break protection for the circuit-breaker OFF command. If a circuit-breaker OFF command is
issued as a result of an overvoltage trip, the circuit-breaker is switched off so that it is fail-safe.
8.4
Fault and system messages
8.4.1

Indicating and rectifying faults

The drive provides many protection functions. These protection functions protect the drive
against damage in a fault situation. A distinction is made between the following messages:
● Fault
● Alarm
The converter indicates a fault by displaying the corresponding fault and/or alarm on the
operator panel.
Faults are displayed as follows:
● By illuminating the red LED "FAULT"
84
WARNING
A fault is a message from the drive indicating a fault or other exceptional (unwanted) state.
The cause can be a fault in the drive itself or also an external fault. This fault, for example,
could have been issued by the winding temperature monitoring of the asynchronous motor.
The faults are displayed and can be reported to a higher-level control system. Once you
have eliminated the cause of the fault, you must acknowledge the fault message.
An alarm is the response to a fault condition identified by the drive, that does not result in the
drive being shutdown. Alarms acknowledge themselves. If the cause is no longer present,
the alarms reset themselves automatically.
Additionally, a note relating to the cause of the alarm is displayed in the status bar of the
operator panel.
SINAMICS SH150 6SL3805
Operating Instructions 05/2020

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents