Screwing The Transport Units Together; Connect To The Foundation; Table 5-2 Tightening Torques For Screw Terminals For Copper Cables Without Cable Lug 1) - Siemens SINAMICS GL150 Operating Instructions Manual

Medium-voltage drive
Table of Contents

Advertisement

Hard S1 materials include steel, for example.
3
Table 5-2
Screw type
M2
M2.5
M3
M3.5
M4
M5
M6
M8
M10
M12
M16
Observe the tightening torques of the terminal manufacturer and the test torques according to
DIN EN 60999-1, VDE 609-1
5.4

Screwing the transport units together

NOTICE
Material damage caused by mechanical pressure on components
Stress that occurs during transport may exert mechanical pressure on the components.
Material damage can result.
● Line the cabinets up precisely with each other in order to avoid shearing forces when the
● Install the converter only on a level and horizontal surface.
5.5

Connect to the foundation

Four holes for M12 screws are provided on each cabinet panel to secure the cabinet to the
foundation. Information on mounting holes and their fixing dimensions are specified in the
dimension drawing.
Install the transport units in accordance with the specifications provided in the accompanying
dimension drawings. When doing this, maintain the specified distance between the top of the
cabinet and the ceiling.
SINAMICS GL150 6SL38555UN113KA0Z
Operating Instructions Rev.201910281450 EXAMPLE
Tightening torques for screw terminals for copper cables without cable lug
Set screws and
headless screws
nm
-
0.25
0.3
0.5
0.8
1.0
1.3
1.8
-
-
-
base units are screwed together.
Head screws with
in - lb
nm
-
2.2
0.5
2.7
0.6
4.4
1.0
7.1
1.3
8.6
2.5
11.5
3.0
15.9
3.9
-
4.8
-
-
-
-
5.5 Connect to the foundation
Head screws with
slit
hexagon profile
in - lb
nm
-
4.4
0.5
5.3
0.6
8.9
1.0
11.5
1.3
22.1
2.5
26.6
3.5
34.5
7.2
42.5
13
-
18
-
30
Mounting
1)
in - lb
4.4
5.3
8.9
11.5
22.1
31.0
63.7
115
159.3
265.5
85

Hide quick links: