Connecting a central fault message facility
L
N
50
Fig. 16

Connecting an AC burner

Pressure-jet oil/gas burner
The burner cables are included in the standard boiler
delivery.
Connect burner to DIN 4791.
Max. power consumption 6 (3) A
41
STB
TR
L1
N T1 T2 S3 B4
Fig. 17
To the control unit
A
To the burner
B
Plug terminal designations
L1
Phase via high limit safety cut-out to the burner
PE
Earth conductor to burner
N
Neutral conductor to burner
T1, T2 Control chain
S3
Burner fault terminal
B4
Hours run meter terminal
:
fA
(cont.)
Rated voltage
Rated current
Signal flow direction:
Control unit
burner
Signal flow direction:
Burner
control unit
Plug equipment codes
fA
STB Control unit high limit safety cut-out
TR
Control unit temperature controller
H1
Burner fault signal
BZ
Hours run meter
90
BN
BK
BU
Fig. 18
To the control unit
A
To the burner
B
Plug terminal designations
T6, T8 Control chain burner stage 2 ON or modulation
controller Open
T6, T7 Control chain burner stage 2 OFF or modula-
tion controller Close
Electrical connections
230 V~
Max. 4(2) A~
:
:
25