Resol BASIC controller Manual For The Specialised Craftsman page 27

Solar controller
Table of Contents

Advertisement

7
OK
COOL
7
OSTC
Store cooling option
PUSH
Adjustment range: OFF / ON
Factory setting: OFF
DTCO
Switch-on temperature diff.
Adjustment range: 1.0 ... 30.0 K
Factory setting: 20.0 K
DTCF
Switch-off temperature diff.
Adjustment range: 0.5 ... 29.5 K
Factory setting: 15.0 K
BACK
PUSH
8
AH O
AH
8
OK
Thermostat switch-on temp.
Adjustment range:
PUSH
0.5 ... 95.0 °C
in steps of 0.5 °C
Factory setting: 55.0 °C
AH F
Thermostat switch-off temp.
Adjustment range:
0.5 ... 94.5 °C
in steps of 0.5 °C
Factory setting: 60.0 °C
t1O
Switch-on time 1
Adjustment range:
00:00 ... 23:45
Factory setting: 00:00
in steps of 15 min
BACK
9
PUSH
7 Cooling function
Note
If the temperature at the store sensor reaches 95 °C, the cooling function
will be blocked. The switch-on hysteresis is -5 K.
Note
If the cooling function is activated, the drainback option will not be avail-
able.
Store cooling
When the store cooling function is activated, the controller aims to cool down the
store during the night in order to prepare it for solar loading on the following day.
If the adjusted maximum store temperature is exceeded and the collector temper-
ature falls below the store temperature, the system will be reactivated in order to
cool down the store.
DTCO and DTCF are used as the reference temperature differences.
8 Afterheating / Thermostat function
t1F
The thermostat function works independently from the solar operation and can
Switch-off time 1
Adjustment range:
e. g. be used for using surplus energy or for afterheating.
00:00 ... 23:45
• AH O < AH F
Factory setting: 00:00
thermostat function for afterheating
• AH O > AH F
t2 (3) O
thermostat function for using surplus energy
Switch-on time 2 (3)
Adjustment range:
In order to block the thermostat function for a certain period, there are 3 time
00:00 ... 23:45
frames t1 ... t3. The switch-on and switch-off times can be adjusted in steps of
Factory setting: 00:00
15 min. If the switch-on and the switch-off times are identical, the time frame is
inactive.
t2 (3) F
If the thermostat function is supposed to run from 06:00 a.m. and 09:00 a.m. only,
Switch-off time 2 (3)
adjust t1 O to 06:00 a.m. and t1 F to 09:00 a.m.
Adjustment range:
If all time frames are set to 00:00, the thermostat function is solely temperature
00:00 ... 23:45
Factory setting: 00:00
dependent.
27