System Programming
The system's Normal programming mode offers several menu options
that are accessible from the main menu screen:
Mode
1. Tx Info
Allows transmitter parameters to be programmed
2. Groups
Allows sets of multiple transmitters to be aggregated
for simpler programming of a common response.
3. Events
Facilitates creation of logical terms which respond to
transmitters or events. These Boolean outputs can
respond to concentration, alarm, or fault status. The‐
se events facilitate voting within a group and can
drive relay outputs.
4. Acqui
Allows the datalogging feature to be activated or de‐
activated
5. Copy
Allows data or parameters to be copied from the
(controller) configuration to parameters
6. Config
Allows system parameters and password to be set
7. Network
Allows actions on the network to be performed,
communication statistics to be consulted, and remote
calibrations to be performed
8. Tests
Allows each device to be tested sequentially (inputs,
outputs, communications, events, etc.) and operation
of various parameters to be validated
9. BACNet
Allows a device's BACNet parameters to be set
10. Wireless
Not supported.
Note: Access to the programming functions is password protected.
The default password is 2967.
The screen display shown below appears initially. This display can be
configured to scroll among the information screens for each device
connected to the controller.
Description