Starting and Stopping Tx Logging
In the previous step, "Acquisition", the frequency at which Tx logs 
would be recorded can be configured. To start the logging function: 
 
When "Start Tx logging" appears on the display, it  indicates that the 
acquisition, or logging, mode is inactive.  When "Stop Tx logging" ap‐
pears, it indicates that Tx data is being logged.  The log message is 
displayed on the screen according to the chosen mode and LED 1 will 
light up. 
 
Press the Enter keypad button to stop or start Tx logging. 
 
When Tx data is logged, the system creates files named 
tayymmdd.log, tbyymmdd.log and tcyymmdd.log, each representing 
one third of the network.  The record includes the transmitter's date, 
time and address, the sensor type, the concentration read, as well as 
the alarm status.  Here is a sample of what a Tx log looks like: 
2004-01-23 17;54;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal-
2004-01-23 17;55;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal-
2004-01-23 17;56;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;0.5;-normal-;003_CO_ppm;0;-normal-
2004-01-23 17;57;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.0;-normal-;003_CO_ppm;0;-normal-
2004-01-23 17;58;25; 001_CO_ppm;0;-normal-;002_NO2_ppm;1.5;-normal-;003_CO_ppm;0;-normal-
These log files are delimited by semicolons and are thus easily read by 
popular spreadsheet programs such as Microsoft Excel. The first col‐
umn of the Tx log displays the date (yyyy‐mm‐dd) and the time 
(hh:mm:ss) of the log.  In this example, the "Delay mode" was set to 
one minute intervals. 
 
The third column of the Tx log displays the transmitter address and 
the fourth displays the gas type, gas concentration and unit of meas‐
urement.   
 
 
 