Requirement: Form NRCA‐PRC‐03‐F step A 4 instructs "Temporarily 
place the system in unoccupied mode and override the programmed 
unoccupied sensor alarm differential from 30% for 4 hours to 1% for 5 
minutes." 
 
Solution: Note that the 301C controller measures deviation in ppm, 
not percent.  Change the event screen to outlier deviation 0 ppm du‐
ration 5 minutes. 
 
 
Note that Honeywell Analytics E3Point CO sensors have a resolution 
of 1 ppm.   
 
 
Requirement: Form NRCA‐PRC‐03‐F step A 5 instructs "Temporarily 
override the programmed occupied sensor proximity zone alarm dif‐
ferential from 30% for 4 hours to 1% for 5 minutes."   
 
Solution: Like step A 4, Set the event screen to deviation 0 ppm and 
duration 5 minutes. 
 
 
 
 
100 
 
 