Action Menu
Actions are comprised of two parameters:
Parameter
Indicates which component is responsible for the action
to be taken;
Tx (transmitter)
Target
Re (Relay/Annunciator)
Ctrl (Controller)
Indicates which of three possible outputs will be activated
when the event is true;
#XX (activates the component's #xx relay),
Relay
Buzzer (activates the component's audible alarm)
ALL (activates the relays and audible alarms)
Example: Tx 007 detects a concentration exceeding the set values.
The target (controller) triggers relay 1 connected to that event (a fan
perhaps). Multiple events may be associated with a single relay. If so,
the relay will be activated if any of the associated events are true.
Description
41