Any service and maintenance work on the panel or system must be carried out by a
trained maintenance engineer from the fire alarm servicing organisation.
Message displayed Description and checks
Loop allocated
Loop device fault
cleared
Loop device
Loop device lost
Loop device
removed
Loop device
replaced
Loop map changed
Loop map saved
Loop not
allocated
Loop Running
Loop Stopped
Loop wiring fault
cleared
Loop wiring
partial short
circuit
Loop wiring short
circuit
Mains supply
Mains supply OK
Maintenance visit
Master alarm 1/2
fault cleared
Master alarm 1/2
open/short
circuit
New password
New Passwords do
not match, try
No devices found
on loop
No MCPs Tested
Panel already
The control panel has completed address allocation of each
device found on the loop.
The fault associated with the loop device has cleared.
There is a hardware fault on the device.
faulty
Replace the loop device.
The device is not communicating.
Check and replace the device if necessary.
A device has been removed from the loop, for example
detector removed from its base.
Re-connect the device on the loop.
A previously removed device has been replaced.
The loop map is different to the one previously allocated.
Check the two map of loop allocations, compare them to find
the difference.
The loop map has been saved.
The loop is not allocated.
Allocate the loop.
The fire detection and alarm function of the loop circuit is fully
operational.
The loop has been powered down and fire/fault detection is
suspended.
The fault associated with loop wiring has cleared.
There is a partial short circuit wiring fault on the loop.
Identify the location of short circuit fault and rectify the faulty
wiring on the loop.
There is a short circuit wiring fault on the loop.
Identify the location of short circuit fault and rectify the faulty
wiring on the loop.
The mains supply to the panel has failed.
failed
Check the mains supply to the panel. Also check the fused
spur to the panel and the mains fuse in the panel.
The mains supply to the control panel is OK.
This message prompts the responsible person to call the
due
servicing organisation to carryout periodical maintenance work
on the system.
The fault associated with the master alarm circuit 1 or 2 has
cleared.
There is an open / short circuit fault on the of master alarm
sounder circuit 1 or 2.
Check the wiring and ensure the end of line resistors are fitted
on the last sounder.
The new password for access levels 2, 3 or 4 had been
saved
changed and saved.
There is a mismatch between copy 1 and copy 2 of the new
password.
again
There were no devices found on the loop circuit.
Following a manual request for weekly fire test message at the
panel no manual call points were tested.
More than one fire reset have been performed on the panel.
reset
There is no need to reset sucessfully reset panel.
796688 (4188-657)_i2 _06/03
67