Local input

Lo cal Input
(ie C la ss C h ang e
op erated b y
a program m er)
C C
C L A S S
C H A N G E
P 1 4
T he local Input can be co nfigured as a
C lass C hange, Fire or E vacuate input.

RS232 interface

S ervice P C
P rin ter
(N ot yet ava ilable )
TX R X 0V
R S 23 2
P 5
C o ntrol p an el
Te rm ina ls P 2 and P 6
sh are a de dica ted R S 2 32
w h ich can be con ne cte d
to either a S ervice PC or P rin ter
18
796688 (4188-657)_ I1.2 / 02.02
The system 800 panel has a local input that can be
configured as a:
Y
class change
10K
Y
fire input
Y
10K
evacuate input
Y
switched OFF
As a class change input the system alarm sounders are
0 V
used for class change application, such as in an
educational establishment like school or college.
As a fire input the panel interprets this as a fire event
and the panel goes into fire condition. The alarm
sounders in the system operate as per a fire event from a
E le ctro nic
M od u le
device on the loop.
As an evacuate input the panel interprets this as a sound
alarms signal and operates the alarm sounders in the
system.
C o n tro l p a ne l
Additionally the local input can be enabled or disabled
using the menu controls at the panel.
If configured as a fire input the panel can put the input
into a Test State.
or
P rin ter
(N ot yet ava ilable )
S ervice P C
P C
TX R X 0V
L IN K
P 6
R S 23 2
P 2
E lec tro nic
M od ule
The system 800 panel has a RS232
interface which can be used to connect the
service PC during commissioning, for
labelling devices and zones in the system.
The RS232 will facilitate the connection of
a printer for printing system events; this is
not yet available.
The terminal block P2 and
connector P6 share a
dedicated RS232 and only
one of these can be used at
any one time.