Common fault output

C o m m o n fa ult ou tpu t via
ch an g e o ve r co n ta cts
ra te d 2 A @ 30 V m a xim um
N C
N O
C
C O M M O N
FA U LT
P 15
C o n trol p a n el
C o n ta cts sho w n w ith the rela y
n o rm a lly e n ergised , th is is th e n o rm a l
o p eratin g sta te.

Auxiliary relay output

A u x ilia ry re la y o u tpu t
v ia v olta g e fre e c on ta c ts
N C N O
C
E le ctro n ic
M od u le
F a cto ry d efa u lt: A u x ilia ry rela y w ill
e n ergis e w ith a fire e v en t a n d is re se t
w ith sy s te m re se t
The system 800 panel has a common output that
operates when the panel goes into a fault condition. The
contacts are shown in their normally energised position
and are rated 2A at 30V maximum. The contacts can be
used to switch external equipment on occurrence of a
fault via the voltage free contacts. The fault output can be
controlled using the fault routing facility.
N o t u se d
I/P 0 V
E le ctro n ic
M o d ule
The system 800 panel has an auxiliary relay that can
operate when a fire event is detected in the system
(default setting). The relay contacts are rated 2A @ 30V
maximum. This output can be used to signal external
equipment in the event of a fire in the system. The relay is
is automatically reset with the following settings:
Relay resets
P 1 6
A U X
System reset
Silence Alarms
Fault removed
Disablement
Pr – prealarm
C o n tro l p a n e l
Fi – Fire
Fa - Fault
Di - Disablement
In addition to the fire mode of operation, it is possible to
configure the relay to operate with a prefire, fault or
disablement conditions.
Common
È È
Pr
Fi
with
'
'
'
'
removed
796688 (4188-657)_I1.2 / 02.02
Fa
Di
'
'
17