Message description list for System 800

Any service and maintenance work on the panel or system must be carried out by a
trained maintenance engineer from the fire alarm servicing organisation.
Message displayed Description and checks
12V supply failed
12V supply OK
24V supply failed
24V supply OK
5V supply failed
5V supply OK
Access codes
Access denied!
Access level
Alarms silenced
Alarms sounded
Allocation Tx
All zones in test
All zones out of
Batteries
discharged
Batteries
disconnected
Battery fault
Cannot put all
zones into test
Cannot test fire
Charger fault
Charger fault
Class change Off
Class change
Clock settings
Customer mode
Data saved
Day mode data
64
796688 (4188-657)_i2 _06/03
The panel 12V supply has failed.
The panel 12V supply is OK.
The panel 24V supply has failed.
The panel 24V supply is OK
The panel 5V supply has failed.
The panel 5V supply is OK
The access codes have been manually reset to the factory
reset
default settings.
The command or menu option selected cannot be executed at
the current access level. Enter a higher access level.
The access level has changed.
changed
The fire alarms in the system have been manually silenced.
The fire alarms in the system have been manually activated
and are sounding.
The panel is not getting a response when communicating with
Error
a device on the loop circuit.
All zones of the system have been manually put into a weekly
fire test state.
All zones of the system have been taken OUT of weekly fire
test
test.
The panel 12V 7Ahr batteries are discharged.
Replace batteries in the panel.
The panel 12V 7Ahr batteries have been disconnected.
The battery disconnection or discharge fault has cleared.
cleared
The panel is in a fire condition and a manual attempt to put all
zones into weekly fire test state is rejected.
Ensure the panel is not in fire condition before putting all zones
into test state.
The panel is in fire condition, therefore manual attempt to test
input
the fire input is rejected.
The battery charger in the panel has developed a fault.
Check the battery circuit wiring and battery fuse.
The fault associated with the battery charger circuit on the
Cleared
electronic module has been cleared.
The class change input has been switched off.
The class change input has been operated and the sounders
operated
in the system are active.
Changes made to the clock settings have been saved.
saved
The customer mode has been entered to allow access to
entered
menu options under level-3.
The changes made to the system configuration has been
saved.
Changes made to the day mode settings have been saved.
saved