To Reset All Configurations And Labels To Factory Settings59; To View Diagnostic Data - Gent System 800 Installer Manual

Fire alarm panel
Hide thumbs Also See for System 800:
Table of Contents

Advertisement

To reset all configurations and labels to factory settings
P 1
1
2
A4
3

To view diagnostic data

A3
A to D
Description of A to D
reference
reading
0
Mains
1
Earth
2
5V
3
12V
4
24V
5
Sounder 1
6
Sounder 2
7
Battery charger
8
Initial battery 1 voltage
9
Initial battery 1 current
10
Final battery 1 voltage
11
EEPROM Charger (PWM)
A fault is indicated if the A to D value is outside the limits.
Lower
Higher
Condition
limit
limit
140
-
Mains fault - Below the lower limit.
74
204
Earth fault – Outside the two limits
223
255
5V supply fault – Outside the two limits
1
255
12V supply fault – Outside the two limits
140
203
24V supply fault – Outside the two limits
58
150
Short circuit fault if belwo the lower limit
Open circuit fault if above the higher limit
58
150
P 1
1
2
3
796688 (4188-657)_i2 _06/03
59