Any service and maintenance work on the panel or system must be carried out by a
trained maintenance engineer from the fire alarm servicing organisation.
Message displayed Description and checks
Day mode entered
Detection devices
config. OK
Detection devices
not zoned
Device disabled /
enabled
Device has no
address
Device isloating
short circuit
Device type
compatible
Device type OK
Device wrong type
Duplicate address
fault cleared
Duplicate address
occurred
Engineering mode
entered
Exit engineering
Exit to level one
External evacuate
activated
External evacuate
fault cleared
External evacuate
operated
External evacuate
Fault routing
disabled
Fault routing
enabled
Fault routing
output fault
cleared
Fault routing
output O/C or SC
Fire input into
Fire input
operated
Fire input reset
The day mode is active. The day mode is automatically exited
after a pre-configured timeout period has elapsed
The detection device assignment has been configured
correctly.
The fire detection devices on the loop are not assigned to
zones. Assign each fire detection device to a zone of the fire
panel.
The device has been manually disabled / enabled.
A new device has been wired on the loop whilst the loop was
running.
The wiring between the displayed devices has a short circuit. If
however the short was on the wiring between the panel and
device then only one device address is displayed.
The device found on the loop is a valid type.
The device type replaced is now OK.
The device replaced is of a different type. Replace like for like
device.
The duplicate addressing fault has cleared.
The panel has found two devices having the same address.
Check the wiring and re-allocate the loop by re-powering the
loop and detection.
The engineering mode has been entered to allow access to
menu options under level-4.
There panel has timed out of engineering mode (level 4).
mode
There has been a manual exit to access level 1 from either
level 2,3 or 4.
The external evacuate (local input) is still active.
The external evacuation (local input) has been cleared.
There has been an external evacuate signal at the local input
and the system alarms are sounding.
The external evacuate signal has been reset for normal
reset
operation.
The fault routing equipment is disabled.
The output signal to fault routing equipment is enabled.
The fault associated with the fault routing output has cleared.
There is a open or short circuit fault between the fire routing
equipment and the control panel. Check the wiring between
the fault routing equipment and fire panel.
The local fire input has been manually put into test state.
test
The local input has signalled a fire condition.
The local fire input has been reset for normal operation.
796688 (4188-657)_i2 _06/03
65