Power up

Battery connection
CAUTION: RISK OF
EXPLOSION IF
BATTERY IS REPLACED
BY AN INCORRECT
TYPE.
DISPOSE OF USED
BATTERIES
ACCORDING TO THE
INSTRUCTIONS.
Battery
Mains supply connection
M ains
S upply
230V
E arth to gland p late
P 3
L
N
F S 7
M ains fus e
3.15A
To power up the panel connect the mains and battery
supply.
Y
Fit the batteries in to the panel, observing the location
and orientation of battery installation.
Y
Connect the wires from the electronic module to both
the batteries.
Y
Ensure the battery link is fitted.
C ontrol panel
G land
A qualified person in accordance with the current
P late
regulations must make the mains supply connection to
the control panel. The mains to the panel must be via a
E lectronic
dedicated 3A fused spur unit, marked in red FIRE ALARM
M odule
– DO NOT SWITCH OFF.
The panel will not power up on battery supply
alone. However in the event of mains failure the
battery will maintain a standby supply to the
panel.
C o ntrol p anel
E lectro nic
FA P
M od ule
F S 3
7A h
+
-
P 8
To prevent serious injury, ensure the mains
supply to the control panel is isolated until
required.
796688 (4188-657)_i2 _06/03
2 X 12 V 7 Ah
B ATT E R Y
23