To Mount The Backbox On Wall - Gent System 800 Installer Manual

Fire alarm panel
Hide thumbs Also See for System 800:
Table of Contents

Advertisement

To mount the backbox
on wall
Cable entry points
Gland plate
Mains cable entry points
Cable tie
1.7m
Fixing points
Floor level
Panel dimensions:
Height 375mm
Width 355mm
Depth 115mm
12
796688 (4188-657)_ I1.2 / 02.02
Ensure there is at least 100mm clearance
around each side of the panel. Also there must
be sufficient space beneath the panel assembly
to allow the door to hang open.
Y
Knockout the required cable entry points from the
backbox or where appropriate snap off the required
cable entry strips from the backbox.
Y
For cable entry from top of enclosure:
S
Cut the cable tie and remove the gland plate from
the back face.
S
Fit gland plate to the inside top face of the
enclosure, with earth terminals towards the front of
the enclosure.
Y
Using the panel wall fixing template mark the four fixing
centres on the wall. Note the panel's top fixing points
should be 1.7m above floor level to the top fixings.
Y
Fix the panel to the wall surface using suitable fixtures
to support the full assembly.
Y
Make use of all four fixing points when securing the
panel to the wall.
Y
Re-fit the door to the backbox.
Y
Fit the electronic module to the back box.
Y
Terminate all the external cables coming into the panel
at required cable entry points.
Y
Mark the cables for connection to the appropriate
terminal block, see cables and wiring details.
E a rth
d ra in
if p a rt o f
th e ca b le
Ba ckbo x
C a ble
C a b le G lan d
G lan d pla te