Kostal PIKO Series Operating Manual page 55

Table of Contents

Advertisement

Installation
1
2
3
Terminal analogue interface (10-pin)
The 10-pin analogue interface terminal is structured as
follows.
Fig. 39: Structure of the 10-pin analogue interface terminal
Voltage output
+12 V: 12 V output for external sensors or for ripple
1
control receivers.
Analogue inputs
AGND: Ground for analogue inputs and S0 input.
2
Aln4-1: Inputs for analogue sensors (0–10 V) or for
3
ripple control receivers.
Pulse meter input
S0-In: The S0 input registers the pulses of an energy
4
meter.
RS485 connections
GND: Ground for RS485.
5
RS485 connections A & B: Serial RS485 interfaces
6
for the connection of external data loggers, displays
and additional inverters.
03 / 2015 | DOC01361707 | KOSTAL operating manual PIKO inverter 3.0 - 20
4
5
6
7
8
9
10
11
INFO
The voltage output is not poten-
tial-free. It can deal with a max.
load of 100 mA.
INFO
Either a PIKO sensor or a ripple
control receiver can be connected
to the analogue inputs Aln1 - Aln4.
INFO
When using the S0 input, the
analogue inputs Aln3 and Aln4
are inactive.
A ripple control receiver can
nonetheless be connected.
12
55