Self-consumption
1
2
3
Activate self-consumption control
Properly connect the external load relay to the
1.
terminal S0/AL-Out.
In the web server, select "Self-consumption control"
2.
or "Dynamic self-consumption control".
Fig. 66, It. 1
Choose function 1 or function 2.
3.
Fig. 66, It. 2
Enter values for the function.
4.
Activate and enter optional value for "Delay in the
5.
event of power loss / fault" with a check box.
Fig. 66, It. 3
Click "Accept".
6.
Start up the inverter.
7.
The self-consumption control function is active.
H
Set up self-consumption control
Connect the inverter and computer with an Ethernet
1.
cable.
Fig. 56
Launch an Internet browser.
2.
Enter the IP address of the master inverter in
3.
the address line of the browser and confirm with
"Return".
The input screen for the access data opens.
P
Enter your user name and password.
4.
The main screen of the web server opens.
P
Click on the "Settings" link.
5.
The "Settings" page opens.
P
In the "Function switch output" menu item, select
6.
the function "Self-consumption control" or "Dynamic
self-consumption control".
Select function 1
7.
Enter values for the function.
8.
03 / 2015 | DOC01361707 | KOSTAL operating manual PIKO inverter 3.0 - 20
4
5
6
Fig. 65
Fig. 67 or 2
Fig. 68.
7
8
9
10
When selecting "Dynamic self-con-
sumption control", the measured
building consumption determined
with the PIKO BA Sensor available as
an option is automatically added to
the set value and taken into consid-
eration.
n You can find more detailed expla-
nations regarding the selection of
function 1 or 2 in the course of the
chapter.
n The command "Delay in the event
of power loss / fault" can be used
for function 1 and 2.
11
12
INFO
INFO
116