Active power control
1
2
3
Activate the active power control
function in the web server
Connect the inverter and computer with an Ethernet
1.
cable.
Fig. 56
Launch Internet browser.
2.
Enter the IP address of the master inverter in the
3.
address line of the browser and confirm with
"Return".
The input screen for the access data opens.
P
Enter your user name and password.
4.
The main screen of the web server opens.
P
Click on the "Settings" link.
5.
The "Settings" page opens.
P
In the menu item "Function analogue inputs", select
6.
the function "Active power control".
Click on the "Accept" button.
7.
The active power control for the ripple control
H
receiver is active.
03 / 2015 | DOC01361707 | KOSTAL operating manual PIKO inverter 3.0 - 20
4
5
6
7
8
9
10
11
IMPORTANT
INFORMATION
The configuration must be carried
out at the master inverter to which
the ripple control receiver is con-
nected. No further adjustments are
necessary for the other inverters.
INFO
The IP address can be queried
by way of the control panel in the
"Settings" menu.
The IP address is found in the inverter
menu under "Settings / Communica-
tion / Network settings 2".
Additional entry options in the
address line of the browser:
S and the serial number of the
inverter on the type plate (example:
http://S12345FD323456)
12
111