Appendix D - Ambient Conditions; Ambient Conditions, Operation; Ambient Conditions, Storage; Ambient Conditions, Transportation - ABB NPBA-12 Installation And Startup Manual

Profibus adapter module
Table of Contents

Advertisement

Ambient Conditions,
Operation
Ambient Conditions,
Storage
Ambient Conditions,
Transportation
NPBA-12 Installation and Start-up Guide
Appendix D – Ambient Conditions
Ambient operating conditions refer to the conditions the option module
is subjected to when installed for stationary use.
Air Temperature: 0 to +50
Relative Humidity: 5 to 95%, no condensation allowed. Maximum
allowed relative humidity is 60% in the presence of corrosive gases.
Contamination Levels:
Chemical gases: IEC 721-3-3, Class 3C2
Solid particles: IEC 721-3-3, Class 3S2
Installation Site Altitude: 0 to 2000 m. If the installation site is above
2000 m, contact local ABB representative.
Vibration: Max 0.3 mm (2 to 9 Hz), max 1 m/s
sinusoidal (IEC 68-2-6)
2
Shock: Max 70 m/s
Ambient storage conditions refer to the conditions the option module is
subjected to during storage in the protective package.
Temperature: -40 to +70
Relative Humidity: Less than 95%, no condensation allowed
Atmospheric Pressure: 70 to 106 kPa
Vibration: Max 0.3 mm (2 to 9 Hz), max 1 m/s
sinusoidal (IEC 68-2-6)
Shock: Max 100 m/s
Ambient transportation conditions refer to the conditions the option
module is subjected to during transportation in the protective package.
Temperature: -40 to +70
Relative Humidity: Less than 95%, no condensation allowed.
Atmospheric Pressure: 60 to 106 kPa
Vibration: Max 3.5 mm (2 to 9 Hz), max 15 m/s
sinusoidal (IEC 68-2-6)
Shock: Max 100 m/s
Bump: Max 300 m/s
Free Fall: 250 mm
°
C
, 22 ms (IEC 68-2-27)
°
C.
2
, 11 ms (IEC 68-2-27)
°
C
2
, 11 ms (IEC 68-2-27)
2
, 6 ms (IEC 68-2-29)
2
(9 to 200 Hz)
2
(9 to 200 Hz)
2
(9 to 200 Hz)
D-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents