Chapter 6 – Communication
Parameters in Cyclic
Communication (DP)
6-10
In cyclic PROFIBUS-DP communication, parameter data is transferred
in PPO message types 1, 2 and 5 (see
Identification part consists of eight bytes (see below).
Parameter
Identification
ID
IND
VALUE
15 14 13 12 11 10
Request Label
Response Label
*Request Signal
*
Not used (=0)
The Request Label is used by the master when transmitting data to the
slave, while the Response Label is used by the slave as a positive or
negative acknowledgement. The tables below show the Request/
Response functions.
Request Labels (from Master to Slave)
Request Function
0
No task
1
Request parameter value
2
Change parameter value (word)
3
Change parameter value (double word)
*4
Request description element
*5
Change description element
*6
Request parameter value (array)
*7
Change parameter value (array word)
*8
Change parameter value (array double word)
*9
Request number of array elements
*Not supported by NPBA-12 SW version V1.0
Figure
Process Data
CW REF
(PD1, PD2...)
SW ACT
9
8
7
6
5
Parameter Number
NPBA-12 Installation and Start-up Guide
6-1). The Parameter
4
3
2
1
0
Response Labels
Ackn. (+)
Ackn. (-)
0
1, 2
7
1
7, 8
2
7, 8
3
7
3
7, 8
4, 5
7, 8
4
7, 8
5
7,8
6
7