Chapter 6 – Communication
Table 6-2 The Status Word (PROFIBUS Parameter 968). The upper case boldface text refers to the
states shown in
Figure
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4
OFF_2_STA
5
OFF_3_STA
6
SWC_ON_INHIB
7
ALARM
8
AT_SETPOINT
9
REMOTE
10
ABOVE_LIMIT
11 to 14
15
6-8
6-2.
Value
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
READY TO OPERATE
0
OFF1 ACTIVE
1
OPERATION ENABLED
0
1
FAULT
0
No fault
1
OFF2 inactive
0
OFF2 ACTIVE
1
OFF3 inactive
0
OFF3 ACTIVE
1
SWITCH-ON INHIBITED
0
1
Warning/Alarm
0
No Warning/Alarm
1
OPERATING. Actual value equals reference value (= is within tolerance limits)
0
Actual value differs from reference value (= is outside tolerance limits)
1
Drive control location: REMOTE
0
Drive control location: LOCAL
1
Actual frequency or speed value equals or is greater than supervision limit
0
Actual frequency or speed value is within supervision limit
Drive-specific
1
Error in DDCS communication (between fieldbus adapter module and drive).
Adapter ceases to communicate with the master
0
DDCS communication OK
STATE/Description