Advertisement

Appendix C – Technical Data

Fieldbus Link

C-2
Compatible Devices: All devices compatible with the PROFIBUS-DP
and PROFIBUS-DPV1 protocols
Size of the Link: 127 stations including repeaters (31 stations and 1
repeater per segment)
Medium: Shielded, twisted pair RS485 cable
• Termination: built in the NPBA-12 Module
• Specifications:
Parameter
Impedance
Capacitance
Resistance
Wire gauge
Conductor area
• Maximum Bus Length (m):
≤ 93.75
187.5
Line A
1200
1000
Line B
1200
600
Topology: Multi-drop
Serial Communication Type: Asynchronous, half Duplex
Transfer Rate: 9.6, 19.2, 44.45, 93.75, 187.5, 500, 1500, 3000, 6000,
or 12000 kbit/s
Protocol: PROFIBUS-DP, PROFIBUS-DPV1
Line A
PROFIBUS-DP
DIN 19245 Part 1
135 to 165
100 to 130
(3 to 20 MHz)
(f > 100 kHz)
< 30
< 110
> 0.64
> 0.34
Transfer Rate (kbit/s)
500
1500
3000
400
200
100
200
NPBA-12 Installation and Start-up Guide
Line B
Unit
< 60
pF/m
/km
> 0.53
mm
2
> 0.22
mm
6000
12000
100
100