ABB NPBA-12 Installation And Startup Manual page 27

Profibus adapter module
Table of Contents

Advertisement

SAP 60 (Slave_Diag)
Byte
1
2
3
4
5 to 6
NPBA-12 Installation and Start-up Guide
This SAP gives diagnostic information on the slave station.
Type: Octet String - Length: 6 (Standard) + 2 (Extended Diagnosis)
Station_Status_1
x
x
x
x
x
x
x
Station_Status_2
x
0
x
x
x
1
x
Station_Status_3
x
0 0 0 0 0 0
Diag.Master_Add
The address of the master that parameterised this slave
Ident_Number (for NPBA-12: 6012h)
Diag_Data (Diagnostic Data)
Description
x
Diag.Station_Non_Existent (Set by Master, reset by Slave)
Slave not found
Diag.Station_Not_Ready (Set by Slave)
Slave not ready for data exchange
Diag.Cfg_Fault (Set by Slave)
Received configuration data does not match original configuration data
Diag.Ext_Diag (Set by Slave)
Diagnostic entry present in slave-specific diagnostic area
Diag.Not_Supported (Set by Slave)
Service not supported by slave
Diag.Invalid_Slave_Response (Set by Master, reset by Slave)
Invalid response by slave
Diag.Prm_Fault (Set by Slave)
Invalid parameter or parameter value
Diag.Master_Lock (Set by Master, reset by Slave)
Slave is parameterised by another master
x
Diag.Prm_Req (Set by Slave)
Slave requires re-configuration and re-parameterisation
Diag.Stat_Diag (Set by Slave)
Static diagnosis. Slave (temporarily) unable to provide valid data
Always set to 1 by Slave
Diag.WD_On (Set by Slave)
Watchdog on
Diag.Freeze_Mode (Set by Slave)
Freeze command received by slave
Diag.Sync_Mode (Set by Slave)
Sync command received by slave
Reserved
Diag.Deactivated (Set by Master, reset by Slave)
Slave is inactive
0
Reserved
Diag.Ext_Diag_Overflow (Set by Slave)
Chapter 6 – Communication