Table 6-1 The Control Word (PROFIBUS Parameter 967). The upper case boldface text refers to the
states shown in
Figure
Bit
Name
0
ON
OFF1
1
OFF2
2
OFF3
3
RUN
4
RAMP_OUT_
ZERO
5
RAMP_HOLD
6
RAMP_IN_
ZERO
7
RESET
8
INCHING_1
9
INCHING_2
10
REMOTE_CMD
11 to 15
NPBA-12 Installation and Start-up Guide
6-2.
Value
1
Proceed to READY TO OPERATE
0
Emergency OFF, stop by the selected deceleration ramp. Proceed to OFF1
ACTIVE; proceed further to READY TO SWITCH ON unless other interlocks
(OFF2, OFF3) are active
1
Continue operation (OFF2 inactive)
0
Emergency OFF, coast to stop.
Proceed to OFF2 ACTIVE; proceed further to SWITCH-ON INHIBITED
1
Continue operation (OFF3 inactive)
0
Emergency stop, stop according to fastest possible deceleration mode. Proceed to
OFF3 ACTIVE; proceed further to SWITCH-ON INHIBITED. Warning: Ensure
motor and driven machine can be stopped using this stop mode.
1
Proceed to OPERATION ENABLED
0
Inhibit operation. Proceed to OPERATION INHIBITED
1
Normal operation.
Proceed to RAMP FUNCTION GENERATOR: OUTPUT ENABLED
0
Stop according to selected stop type
1
Normal operation.
Proceed to RAMP FUNCTION GENERATOR: ACCELERATOR ENABLED
0
Halt ramping (Ramp Function Generator output held)
1
Normal operation. Proceed to OPERATING
0
Force Ramp Function Generator input to zero
0 Þ 1 Fault reset if an active fault exists. Proceed to SWITCH-ON INHIBITED
0
(Continue normal operation)
Inching 1. (See the drive documentation for information)
Inching 2. (See the drive documentation for information)
1
Fieldbus (DDCS) control enabled
0
Control Word <> 0 or Reference <> 0: Retain last Control Word and Reference
Control Word = 0 and Reference = 0: Fieldbus (DDCS) control enabled
Drive-specific. (See the drive documentation for information)
Proceed to STATE/Description
Chapter 6 – Communication
6-7