Appendix A - Profibus Parameters - ABB NPBA-12 Installation And Startup Manual

Profibus adapter module
Table of Contents

Advertisement

PROFIBUS
Parameter Name
Par. No.
918
NODE ADDRESS
947
FAULT NUMBER
963
CURRENT BAUD RATE
964
DEVICE IDENTIFICATION
965
PROFILE NUMBER
967
CONTROL WORD
968
STATUS WORD
971
STORE
NPBA-12 Installation and Start-up Guide
Appendix A – PROFIBUS Parameters
The table below shows the PROFIBUS Profile-specific Parameters. All
these values are of the "unsigned16" data type.
R/W
Description
R
Node address of the device
Allowable values: 2, ..., 126
R
The last fault occurred in the drive
0h = No fault
1000h = Generic fault
R
Detected baud rate
0 = 12 Mbit/s
1 = 6 Mbit/s
2 = 3 Mbit/s
3 = 1.5 Mbit/s
4 = 500 kbit/s
5 = 187.5 kbit/s
6 = 93.75 kbit/s
7 = 45.45 kbit/s
8 = 19.2 kbit/s
9 = 9.6 kbit/s
255 = Invalid baud rate
R
Identification number of this device (6012h)
R
Profile number of this device (0302h)
R
16-bit word for controlling the drive
R
16-bit word indicating drive status
R/W
0 = No action
1 = Save drive parameters to non-volatile memory