PROFIBUS
Parameter Name
Par. No.
918
NODE ADDRESS
947
FAULT NUMBER
963
CURRENT BAUD RATE
964
DEVICE IDENTIFICATION
965
PROFILE NUMBER
967
CONTROL WORD
968
STATUS WORD
971
STORE
NPBA-12 Installation and Start-up Guide
Appendix A – PROFIBUS Parameters
The table below shows the PROFIBUS Profile-specific Parameters. All
these values are of the "unsigned16" data type.
R/W
Description
R
Node address of the device
Allowable values: 2, ..., 126
R
The last fault occurred in the drive
0h = No fault
1000h = Generic fault
R
Detected baud rate
0 = 12 Mbit/s
1 = 6 Mbit/s
2 = 3 Mbit/s
3 = 1.5 Mbit/s
4 = 500 kbit/s
5 = 187.5 kbit/s
6 = 93.75 kbit/s
7 = 45.45 kbit/s
8 = 19.2 kbit/s
9 = 9.6 kbit/s
255 = Invalid baud rate
R
Identification number of this device (6012h)
R
Profile number of this device (0302h)
R
16-bit word for controlling the drive
R
16-bit word indicating drive status
R/W
0 = No action
1 = Save drive parameters to non-volatile memory
A-1