Commissioning

Note:
Up to device version /CC, the CC-CO is delivered with the jumper settings
"MASTER" and "OPERATION".
For pairwise operation, one converter must be reconfigured by plugging
the jumper into the "SLAVE" position (see Fig. 13).
For device version /DD and higher, the CC- CO is delivered with the
jumper settings "MASTER", "NORMAL" and "OPERATION".
For pairwise operation, one converter must be reconfigured by plugging
the jumper into the "SLAVE" position (see Fig. 15).
Opening the CC–CO
Switch off or disconnect the auxiliary supply voltage at both poles.
Open the CC–CO. To open the case you must release the six screws at the cover with a
screwdriver (see Fig. 18).
42
DANGER!
Before opening the CC–CO all poles must be disconnected from
the auxiliary voltage supply! There is danger to life by energized
parts in the converter.
7XV5662-0AC01
C53000-B1174-C165-4