Siemens 7XV5662-0AC01 Manual page 43

Communication converter for pilot wires. asynchronous interface
Table of Contents

Advertisement

Available languages

Available languages

7XV5662-0AC01
Configuration of the CC–CO (up to device version /CC)
Operating and Test mode:
CC-CO, device version up to /CC or module version up to C53207-A338-B5-3
The CC–CO is configured by means of jumpers. The jumper positions for master and slave
configuration are illustrated in Fig. 13, for Test mode in Fig. 14.
One converter must be configured as a Master-device and the other converter as a Slave-
device.
Master mode/operating
see Fig. 13, on the left
Slave mode/operating
see Fig. 13, on the right
Master
MASTER
SLAVE
OPERATION
TEST
*
SIEMENS
kuku
Figure 13 Jumper location for master and slave configuration
Note: It is of no importance which of the CC–COs used is set to master and
which to slave mode. It must only be ensured that both a master and a slave are
connected to the communication link.
C53000-B1174-C165-4
*
Slave
MASTER
SLAVE
OPERATION
TEST
*
*
SIEMENS
kuku