Siemens 7XV5662-0AC01 Manual page 53

Communication converter for pilot wires. asynchronous interface
Table of Contents

Advertisement

Available languages

Available languages

7XV5662-0AC01
Specifications
Electrical Tests
Standards:
Insulation Tests
Standards:
– High Voltage Test (routine test)
only power supply and GOK
– High Voltage Test (type test)
Line a/b
– Impulse Voltage Test (type test)
all circuits except communications and
time synchronization interfaces, Class III
– Impulse Voltage Test (type test)
Communication interfaces
(Line a/b)
EMC Tests for Immunity (Type Tests)
Standards:
– High Frequency Test
IEC 60255-22-1, Class III and
VDE 0435 Part 303, Class III
– Electrostatic Discharge
IEC 60255-22-2 Class IV and
IEC 61000-4-2, Class IV
– Irradiation with HF Field,
frequency sweep
IEC 60255-22-3 Class III
IEC 61000-4-3, Class III
– Irradiation with HF Field,
single frequencies
IEC 60255-22-3, IEC 61000-4-3, Class III
C53000-B1174-C165-4
IEC 60255 (Product Standards)
ANSI/IEEEC37.90.0,.C37.90.0.1,
C37.90.0.2
DIN 57435 Part 303
See also standards for following individual
tests
IEC/EN 61010-1, IEC 60255-5 and
IEC 60870-2-1
DC: 3.5 kV
DC: 7 kV
5 kV (peak); 1.2/50 µs; 0.5 Ws; 3 positive
and 3 negative impulses in intervals of 5 s
10.2 kV (peak); 1.2/50 µs; 0.5 Ws;3 positive
and 3 negative impulses in intervals of 5 s
IEC 60255-6 and -22, (Product Standards)
EN 61000-6-2 (Generic Standard)
VDE 0435 Part 301 DIN VDE 0435-110
2.5 kV (Peak); 1 MHz; τ = 15 µs;
400 Surges per s; test duration 2 s;
= 200 Ω
R
i
8 kV contact discharge;
15 kV air discharge; both polarities;
= 330 Ω
150 pF; R
i
10 V/m; 80 MHz to 1000 MHz; 80 % AM;
1 kHz
20 V/m; 1.4 GHz to 2.0 GHz; 80 % AM;
1 kHZ
10 V/m; 800 MHz to 960 MHz; 80 % AM;
1 kHz
10 V/m
English
53

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

7xv5662-0ac00

Table of Contents