Configuring the CC–CO (device version /DD and higher)
Operating and Test mode:
CC-CO, device version /DD and higher or module version up to C53207-A338-B7-1
The CC-CO is configured by means of jumpers. The jumper positions for master and slave
configuration are illustrated in Fig. 15, for Test mode in Fig. 16.
One converter must be configured as master device and the other converter must be
configured as slave device.
Master/Operation setting
See Fig. 15, on the left. The fourth jumper remains in its original position.
Slave/Operation setting
See Fig. 15, on the right. The fourth jumper remains in its original position.
Master
Figure 15 Jumper location for master and slave configuration
C53000-B1174-C165-4
** not changing
delivering position
English
Slave
** not changing
delivering position
45