connect –48 V from feed B to the input terminals of the second power supply on the other side of the
chassis. This configuration provides the commonly deployed A/B feed redundancy for the system.
To connect the power supply to the power source:
a. Secure the ring lug of the positive (+) DC power source cable to the V+ terminal on the DC power
supply.
b. Secure the ring lug of the negative (–) DC power source cable to the V– terminal on the DC power
supply.
c. Tighten the screws on the power supply terminals until they are snug by using the screwdriver. Do
not overtighten—apply between 5 lb-in (0.56 Nm) and 6 lb-in (0.68 Nm) of torque to the screws.
8. Replace the terminal block cover.
9. Close the input circuit breaker.
10. Verify that the DC LEDs are lit green and on steadily.

Step 5: Perform Initial Software Configuration

This procedure connects the router to the network but does not enable it to forward traffic. For complete
information about configuring the router to forward traffic, including examples, see the Junos OS
configuration guides.
You must perform the initial configuration of the router through the console port. Before you begin, set
the following parameter values in the console server or PC:
Baud Rate—9600
Flow Control—None
Data—8
Parity—None
Stop Bits—1
DCD State—Disregard