Section 3: Dip Switch Definition - YASKAWA MotionSuite MP940 Hardware Manual

Machine controller
Table of Contents

Advertisement

MotionSuite™ MP940 Machine Controller Hardware Manual

Section 3: DIP Switch Definition

The function of the six switches is explained in the table below.
Number
Name
6
RUN
5
INIT
4
TEST
3
FLASH
2
Programming
Port Default
1
COPY
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
RUN
INITIAL
TEST
FLASH
P.P
COPY
NO
Figure 3.1: MP940 DIP Switches
DIP Switch Settings
Setting
ON
Application program runs at power ON
OFF
Application program does not run at power ON
ON
When DIP switch 4 is OFF:
Data is copied from flash memory to RAM at power ON.
When DIP switch 4 is ON:
Memory is cleared.
OFF
When DIP switch 4 is OFF:
Data is not copied from flash memory to RAM at power ON.
When DIP switch 4 is ON:
Nothing
ON
Terminal Mode/Initialization Mode
OFF
Online
ON
Program is copied from flash memory to RAM at power ON.
OFF
Program is not copied from flash memory to RAM at power ON
ON
Defaults to Port 1 only
OFF
The programming port is set up through software selection
ON
Global variables are copied from flash at power ON
OFF
Global variables are not copied from flash at power ON.
15
Section 3: DIP Switch Definition
Function
Default
Setting
ON
OFF
OFF
OFF
OFF
OFF