6. Adjustment

6.1 DIP switches
The DIP switches on the printed circuit board are used to adjust the air volume for
each ventilator. The upper row of DIP switches controls the extractor ventilator and
the lower row controls the supply ventilator. Because both ventilators can be set inde-
pendently, it is possible to create a difference in the amount of air. This can be used
when a negative or positive pressure is desired.
Extractor ventilator
Supply ventilator
Procedure
1.
Close the windows and doors
2.
Open the extractor valves and supply valves to the maximum
3.
Remove the plug of the balance ventilation unit from the wall socket
4.
Unclip the filter covers and check whether the filters are clean. Clean or replace if
necessary. Replace the filter covers
5.
Unscrew the 2 screws on the top of the printed circuit board cover using a Torx
screwdriver (T25). The printed circuit board cover can then be detached from the
unit housing, the DIP switches on the printed circuit board are now accessible.
Caution: The display cable in the cover is attached to the print. Open the cover
carefully to prevent cable breakage
6.
Set the desired air volume for both ventilators with the DIP switches. See the
table and image below
7.
Restart the unit and adjust the unit to setting 2 or 3
8.
Measure the total air volume on the Orcon extractor and supply valves and adjust
the air volume for each ventilator if necessary
9.
Set the valves to the correct flow rate per room
10. Completing the installation report (see Chapter 9)
11. Replace the printed circuit board cover and screw it down tightly