4.4 Electric connectors
The HRC is equipped with a earthed
power cord as standard. Optionally,
you can replace the earthed power
cord with a perilex cord (article
number: 22915405).
The place where the wall socket
needs to be fitted is indicated in
the figure below. The electrical
installation must comply with
NEN1010 and the requirements
of the local energy company.
Only place the plug in the
wall socket when the entire
installation is ready and no
building material is present
The unit is not suitable for
3-phase current
Supply voltage:
230 Volt ~50 Hz
Fitting the HRC with a perilex cord
Caution: ensure that the unit is always disconnected from the power supply
when changing the earthed power cord.
If you want to replace the earthed power cord with a perilex power cord, follow these steps:
1.
Place the unit on a flat surface.
2.
Remove the earthed power cord from the cable clamp on the metal rear frame
3.
Remove the printed circuit board cover on the top of the unit by unscrewing the 2
screws using a Torx screwdriver (key size T25)
4.
Remove the connector from connection X27
5.
Remove the earthed power cord from the cable recess.
6.
Using a flat screwdriver, attach the black wire of the perilex cord to position 2
(centre) of screw connector X9.
7.
Using a flat screwdriver, attach the black wire of the perilex cord to position 3
(under) of screw connector X9.
12
Location of socket
outlet relative to
wall bracket
index