Parameter
Domestic hot water
0C For solar DHW heating: DHW temperature target
Display
40 °C
None
... °C
0D With 2 tank temperature sensors: Tank heating stop point
Display
...
...
0E With 2 tank temperature sensors: Tank heating start point
Display
...
...
0F Runtime, actuator, mixing valve, heat exchanger set, Vitotrans 222
Display
75 s
... s
11 Runtime, primary cylinder loading pump, heat exchanger set
Display
10 s
... s
76
(cont.)
Value
0C:40
0C:0 to
0C:9
0C:10 to
0C:95
Value
0D:8
0D:2 to
0D:10
Value
0E:7
0E:1 to
0E:9
Value
0F:75
0F:10 to
0F:255
Value
11:10
11:0 to
11:30
!
Explanations
Reheating is suppressed above the selected set tem-
perature (DHW heating by the boiler only if solar en-
ergy is insufficient).
Note parameter "01" setting.
Set DHW temperature 40 °C
No set value 3
Entry of a 2nd set DHW temperature
Explanations
Displayed only if parameter "00:2" has been set.
Cylinder heating stop point at set value x 0.8
Adjustable from 0.2 to 1
≙
1 step
0.1
Explanations
Displayed only if parameter "00:2" has been set.
Cylinder heating stop point at set value x 0.7
Adjustable from 0.1 to 0.9
≙
1 step
0.1
Explanations
Displayed only if parameter "00:3" has been set.
Explanations
Displayed only if parameter "00:3" has been set.
Cycling of the secondary cylinder loading pump for
the cylinder loading system in the start phase of the
system.
Setting is subject to the type of circulation pump (con-
nection at plug
)
sA
The secondary cylinder loading pump for the cylinder
loading system is switched on cyclically for 10 s.