Pump Or/And 3-Way Mixing Valve - Viessmann Vitotronic 11 CC1E Installation And Service Instructions Manual

Table of Contents

Advertisement

Boiler water temperature control
20 A1
20
N
L
A
K
close
close
close
1
2
n
B
Fig. 37
A1 Closing of mixers
Contactor relay, part no. 7814 681
A
Downstream heating circuit controller, switching
B
contact closed:
Signal for mixer CLOSE
Multi boiler system
Plug
A1 of the Vitotronic is used as a switching
contact for the Therm-Control.
Required parameter: "0D:1" in the "Boiler" group
and "53:2" in the "General" group
Boiler protection function: Raising the return temperature via shunt pump or/and 3-way mixing
valve
With shunt pump
For heating systems with distributor installed close to
the boiler
With 3-way mixing valve:
For heating systems where downstream heating cir-
cuits cannot be controlled, e.g. older systems or
commercial nurseries.
Conditions:
The boiler water flow rate must be able to be
reduced by at least 50 %.
With shunt pump:
Size the shunt pump to approx. 30 % of the total
throughput.
With 3-way mixing valve:
Size the boiler circuit pump at each boiler to
approx. 110 % of the total throughput.
Also affects the heating circuits.
(cont.)
L1
C
N
PE
A1
N
L1
K1
A
Fig. 38
A1 Closing of mixers
Contactor relay, part no. 7814 681
A
Downstream heating circuit controller, switching
B
contact closed:
Signal for mixer CLOSE
Power supply, 230 V/50 Hz
C
Junction box, on site
D
Function
Single boiler systems and multi boiler systems
with shunt pump
Temperature sensors T1 and T2 capture the return
temperature at different test points.
The shunt pump is started via temperature sensor T2
if the factory-selected minimum return temperature
(specified by the coding card) is not being achieved.
The flow rate will be reduced via the mixers if the
minimum return temperature captured by tempera-
ture sensor T1 is not achieved despite return temper-
ature raising.
Single boiler systems with shunt pump and 3-way
mixing valve
Temperature sensors T1 and T2 capture the return
temperature at different test points.
The shunt pump is started via temperature sensor T2
if the factory-selected minimum return temperature
(specified by the coding card) is not being achieved.
The flow rate will be reduced via the 3-way mixing
valve if the minimum return temperature captured by
temperature sensor T1 is not achieved despite return
temperature raising.
Function description
K1
K2
A1
N
L1
K3
K2
A
A
B
1
D
2 ... n